Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/23/2024 | Bldg Permits - Post Review | REVIEW COMPLETED | |||
05/23/2024 | External Reviewers - SAFEBuilt | REVIEW COMPLETED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 4/5/2024 11:35:01 PM Building(B) Reviewer Keith Miller kmiller@safebuilt.com Approved Reason: Date Completed : 5/23/2024 9:04:49 AM The plans are approved. Subject to the field inspector's approval. Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 4/1/2024 4:32:29 PM 1. Need to coordinate RTU-1 electrical OCP and conductor feeds to support Mechanical revision change as called out on sheet M01.01 Rooftop Heat Pump Schedule 'Electrical'. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved Reason: Date Completed : 5/20/2024 10:59:31 PM Revised plan Plumbing Review: OK Resolved-1). Plan Sheet P03.01: lift tank detail is missing the shut off valve. Add the required shut off valve on the discharge side of the check valve in accordance with -2018 IPC 712.2 |
||
05/20/2024 | PDSD Application Completeness | REVIEW COMPLETED |