Permit Number: TC-COM-1123-02668
Parcel: 10511061R

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1123-02668
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2024 Bldg Permits - Post Review REVIEW COMPLETED
05/23/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 4/5/2024 11:35:01 PM



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 5/23/2024 9:04:49 AM
The plans are approved. Subject to the field inspector's approval.



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 4/1/2024 4:32:29 PM
1. Need to coordinate RTU-1 electrical OCP and conductor feeds to support Mechanical revision change as called out on sheet M01.01 Rooftop Heat Pump Schedule 'Electrical'.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 5/20/2024 10:59:31 PM
Revised plan Plumbing Review: OK
Resolved-1). Plan Sheet P03.01: lift tank detail is missing the shut off valve. Add the required shut off valve on the discharge side of the check valve in accordance with -2018 IPC 712.2
05/20/2024 PDSD Application Completeness REVIEW COMPLETED