Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1123-02659
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/16/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/16/2023 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-1123-02656 (1625 W FORT LOWELL RD Unit:UNIT 59-66 TUCSON, AZ 85705) TC-COM-1123-02657 TC-COM-1123-02658 TC-COM-1123-02659 TC-COM-1123-02660 TC-COM-1123-02661 TC-COM-1123-02662 TC-COM-1123-02663 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Show the unit number on the site plan for each service meter. 2. Provide a grounding detail in compliance with NEC 250. Show grounding rods(2x) at each new Mobile home panelboard, NEC 250.32(A). 3. Show on the plans that each of the new Mobile home panelboards shall be suitable for use as service equipment, per NEC 550.32. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 11/14/2023 | PDSD Application Completeness Express | REVIEW COMPLETED | Shared Studio Session on 906-969-673 Master Permit is TC-COM-1123-02656 relocate the pedestal to a meter pack. Permits running off Master Permit Plan set TC-COM-1123-02657, TC-COM-1123-02658, TC-COM-1123-02659, TC-COM-1123-02660, TC-COM-1123-02661, TC-COM-1123-02662 & TC-COM-1123-02663. |