Permit Number: TC-COM-1123-02617
Parcel: 132130930

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1123-02617
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2024 Site Zoning APPROVED
02/08/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/06/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1.Ref; Submitted plans. Why are there 2 different sets of electrical plans submitted by 2 different registrants that do not correlate with each other? Please submit 1 set of electrical plans that accurately show the entire scope of electrical work.

2. The electrical line diagram is not complete.

2a. Show all feeders. Secondary Service conduit and conductor quantities, sizes and types.

2b. KEYED NOTES #1. Could not locate the feeder schedule as indicated.

3a. Whichever plan(s) are to be used, provide complete Outdoor Lighting compliance for the entire site as required per section 104 of the 2012 City of Tucson Outdoor Lighting Code.

3b. Whichever plan(s) are to be used, please include a complete power and lighting site plan.

Be advised, the City of Tucson's electrical review ends at the Modular Building. Everything exterior or not attached to the Modular Building will be reviewed for electrical by COT, including the site Outdoor Lighting.

Ref’ 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
02/08/2024 Commercial Plumbing REQUIRES RESUBMIT Based on the FFE shown on the grading plan (sheet 11 0f 16), the rim elevation of the next upstream sanitary manhole (2494.79) is less than 12” below the first floor elevation (2495.55). Provide a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.]
01/16/2024 Fire New Construction REVIEW COMPLETED
01/11/2024 PDSD Application Completeness REVIEW COMPLETED