Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1123-02617
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/28/2023 | Commercial Structural | APPROVED | I concur with Tucson Fire Department, this is a B occupancy type (not F-1). My approval is contingent on this correction being made. Should this correction not made, my approval is void. | ||
12/14/2023 | Site Engineering | APPROVED | |||
12/05/2023 | Water - PDSD | APPROVED | |||
12/05/2023 | Commercial Mechanical | NOT REQUIRED | |||
12/14/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/06/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Provide a complete line diagram and grounding detail for the new electrical service and downstream subpanel. 2. Provide complete compliance with the 2012 City of Tucson Outdoor Lighting code for the exterior lighting. See Chapter 104 for Outdoor Lighting Plan and permit Submittal requirements. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |
||
12/04/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Revise the site plan to show the size of the water meter and the backflow preventer. Reference: Section 107.2.1, IBC 2018. 2. Revise the site plan to show sufficient dimensions and notes to construct the building sewer and the grease interceptor. Reference: Section 107.2.1, IBC 2018. 3. Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. |
||
11/22/2023 | Fire New Construction | REQUIRES RESUBMIT | Your code analysis states this project is an F1. Verify it is an F1 by definition and not a B occupancy. John.vincent@tucsonaz.gov 5203495581 |
||
11/22/2023 | Site Zoning | REQUIRES RESUBMIT | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: TC-COM-1123-02617 1610 E TUCSON MARKETPLACE BL Zoning PAD-15 Food Service TRANSMITTAL DATE:‎November 22, 2023 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: Please provide a complete plan set which will include the site plan. If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
||
11/16/2023 | PDSD Application Completeness | REVIEW COMPLETED |