Permit Number: TC-COM-1123-02605
Parcel: 10925032A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1123-02605
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2023 Water - PDSD APPROVED
12/12/2023 Site Engineering NOT REQUIRED
12/12/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/24/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved with Comments
Reason:
Date Completed : 11/22/2023 12:07:31 PM
1. S-301 - MECHANICAL UNITS: The Mechanical Roof Plan, M-201, calls out a rooftop mechanical unit "AC-9" at approximately Gridline E/6.5. The proposed unit weighs 780 lb. Please confirm that the existing roof framing is sufficient to support this additional load and no retrofitting is required.

2. S-101 - CONFLICTING INFORMATION: Please confirm the minimum size for wood blocking members below a new mechanical unit. Details 10/S-101 and 1 & 2/S-501 provide conflicting information (4x6 vs 4x10, typical).

3. S-101 - CONFLICTING INFORMATION: Please confirm the minimum size for Typical Opening Framing members. Details 5 and 9/S-101 provide conflicting information (2x6's vs. 2x12's for a 4-ft opening)



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 11/22/2023 1:26:04 PM
1. Sheet G-003: The listed building code is not an adopted and applicable code enforced by the City of Tucson. Provide a building code that is adopted and enforced by the City of Tucson.

2. Sheet G-003: There is a distinct difference between occupancy classification and occupancy use. The classifications provided in Section 304.1 apply to that of classification and the requirements of max. allowable area, height, stories, mix-use requirements and overall classification of the building. Therefore, this structuring is considered as business in the overall context of the structure and can comply with the business requirements previously mentioned. However, when calculating occupant loads, one must calculate based on the use of the space. The patient spaces are of an institutional use and the occupant load must be calculated as such in accordance with Section 1004 and Table 1004.5. Provide an occupant load calculation in accordance with 2018 IBC Section 1004.3 and Table 1004.5.

3. Sheet A-102: The medical gas room door is not rated appropriately. Provide a properly rated door for the medical gas room in accordance with 2018 IBC Section 427.2.1.

4. Sheet A-102: The medical gas room is not vented properly. Provide a properly vented medical gas room in accordance with 2018 IBC Section 427.2.1.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 11/14/2023 9:07:10 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 11/20/2023 11:56:56 AM
Electrical Review of AJSC Center
By: Ron Ross PE
ED-100 Electrical Demo Plan: Could not locate Keyed Note #3 and missing Keyed Note #5. Same?



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 11/23/2023 11:00:27 PM
First Plumbing Review:
1). Need to address Building plan review comments 2 -IPC 403.1

2). Door for room #132 on plan page A-601 needs to have door label that complies with NFPA99 5.1.3.1.9

3). Air compressor location not clear on plan pg MG1 - IPC 106.3.1

4). Add air compressor detail to plan page MG2, does compressor need a drain? -IPC 106.3.1
11/21/2023 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL
FROM: PDSD Zoning Review
PROJECT: TC-COM-1123-02605 / TI
Plot Plan Review (1st Review)
4745 E Camp Lowell Dr / O-3
TRANSMITTAL DATE: 11/21/2023

1.COMMENT: Alterations and additions to a commercial site including the addition of the generator require a Development Package (MINOR DEVELOPMENT CHANGES TO EXISTING COMMERCIAL/INDUSTRIAL SITES) A Development package is a separate submittal and must be submitted and approved prior to the approval of the commercial plans.

Information on development packages can be found here:
Checklist for minor development changes to exiting commercial site
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf

Resubmittal instructions: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf

For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov
11/22/2023 Fire New Construction REVIEW COMPLETED
11/09/2023 PDSD Application Completeness Express REVIEW COMPLETED