Permit Number: TC-COM-1123-02605
Parcel: 10925032A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1123-02605
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/30/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved with Comments
Reason:
Date Completed : 11/22/2023 12:07:31 PM

1. S-301 - MECHANICAL UNITS: The Mechanical Roof Plan, M-201, calls out a rooftop mechanical unit "AC-9" at approximately Gridline E/6.5. The proposed unit weighs 780 lb. Please confirm that the existing roof framing is sufficient to support this additional load and no retrofitting is required.

2. S-101 - CONFLICTING INFORMATION: Please confirm the minimum size for wood blocking members below a new mechanical unit. Details 10/S-101 and 1 & 2/S-501 provide conflicting information (4x6 vs 4x10, typical).

3. S-101 - CONFLICTING INFORMATION: Please confirm the minimum size for Typical Opening Framing members. Details 5 and 9/S-101 provide conflicting information (2x6's vs. 2x12's for a 4-ft opening)



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 1/29/2024 10:51:00 AM

1. Sheet G-003: The listed building code is not an adopted and applicable code enforced by the City of Tucson. Provide a building code that is adopted and enforced by the City of Tucson.

◦ NOTE: Sheet G-003 indicates the use of the City of Tempe Building Safety Administrative Code. Remove this from the governing codes box.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 11/14/2023 9:07:10 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 11/20/2023 11:56:56 AM
Electrical Review of AJSC Center
By: Ron Ross PE

ED-100 Electrical Demo Plan: Could not locate Keyed Note #3 and missing Keyed Note #5. Same?



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 1/29/2024 10:27:41 PM
Second Plumbing Review:

Resolved-1). Need to address Building plan review comments 2 -IPC 403.1

Resolved-2). Door for room #132 on plan page A-601 needs to have door label that complies with NFPA99 5.1.3.1.9

Resolved-3). Air compressor location not clear on plan pg MG1 - IPC 106.3.1

Resolved-4). Add air compressor detail to plan page MG2, does compressor need a drain? -IPC 106.3.1
02/12/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1123-02605
4745 E CAMP LOWELL DR. – I-1
Medical Service Outpatient, excluding blood donor centers (2nd Review)

TRANSMITTAL: February 12, 2024

Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in O-3 (UDC 4.7.15). Medical Service Outpatient is an allowed use in the zone (UDC Table 4.8-3) subject to Use Specific Standards 4.9.13.K.

1. COMMENT: Alterations and additions to a commercial site including the addition of the generator require a Development Package (MINOR DEVELOPMENT CHANGES TO EXISTING COMMERCIAL/INDUSTRIAL SITES) A Development package is a separate submittal and must be submitted and approved prior to the approval of the commercial plans. Information on development packages can be found here: Checklist for minor development changes to exiting commercial site https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf Resubmittal instructions: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/25/2024 PDSD Application Completeness Express REVIEW COMPLETED