Permit Number: TC-COM-1123-02604
Parcel: 117067310

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1123-02604
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2023 Design Review APPROVED Plans show existing doors/windows, patio, fencing, access are being maintained.
11/21/2023 Site Zoning APPROVED
12/05/2023 Water - PDSD APPROVED
12/12/2023 Site Engineering NOT REQUIRED
12/12/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/21/2023 External Reviewers - Willdan REQUIRES RESUBMIT Questions for review comments contact Bill McClellan by email at bmcclellan@willdan.com or message on cell #(928)580-3179 COPY svasquez@willdan.com.
1. Sheet a0.1 Clarify type of construction per IBC table 601, not complete (BM)
2. Sheet a3.1 Provide details for "H" system , sliding or stationary, aluminum framed or track, height, attachment to floor and structure above, door and hardware and safety glazing. Per IBC 107.2.1 (BM).
3. Sheet a3.1 Nonabsorbent wall surfaces at all water closets & urinals will need to meet requirements of IBC 1209.2.2 @ a minimum of 4' AFF at rear and side walls within 24" of fixture. Clarify on details on sheet a8.1 & notes on this sheet. (BM)
4. Sheet a3.1 Verify wall covering D meets requirements for hood location if type 1 hood is installed as per IMC 507.2.6 (BM)
5. Sheet fs1.0 See notes on sheet m2.0
6. Sheet m2.0 Provide manufactures data in plans for exhaust hood & exhaust system to meet IMC section 506.5 & 506.3.13.2 for installation work clearances and termination location. Clarify in plans and per AHJ that IMC section 507.2 & 509 are not applicable. Not clear in plans. (BM)
7. Sheet m2.0 Clarify if opening for exhaust louver is new. Will need to provide framing and structural detail is not existing. IBC 107.2.1 (BM)
8. Sheet e2.0 Identify all existing or new EM lights, exit signs & EM egress lights to meet IBC section 1008 & 1013. Not clear on plan sheet (BM)
11/22/2023 Fire New Construction REQUIRES RESUBMIT -Indicate what type of hardware will be on gate located on west side of bldg.
-Three doors are currently listed as being primary entrances. All three are not primary entrances (main exit). Provide panic hardware on exit doors that are not main exits per 1010.1.10.
- Identify all existing or new EM lights, exit signs & EM egress lights to meet IBC section 1008 & 1013. Include required EM lighting on patio.
john.vincent@tucsonaz.gov
5203495581
11/09/2023 PDSD Application Completeness REVIEW COMPLETED