Permit Number: TC-COM-1123-02604
Parcel: 117067310

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1123-02604
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/15/2024 External Reviewers - Willdan REQUIRES RESUBMIT Contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179 for review comment querstions
1. Sheet m2.0 Mechanical sheet m3.0 & m4.0 have equipment and schedules removed, all plan sheets need to be updated to identify changes per 2018 IBC 107.2.1 (BM)
2. Sheet e1.0 Detail title lettering needs to be corrected per 2018 IBC 107.2.1 (BM)
3. Sheet e2.0 Prior comment for egress lighting has not been completed 2018 IBC 107.2.1 (BM)
4. Sheet e3.0 Detail title lettering needs to be corrected per 2018 IBC 107.2.1 (BM)
5. Sheet e3.0 Per conversation with Jacob with FORS design team, some proposed appliances have been removed from scope of work, will need to adjust panel schedules and calculations per 2018 IBC 107.2.1 (BM)
05/07/2024 Fire New Construction REVIEW COMPLETED
05/03/2024 PDSD Application Completeness REVIEW COMPLETED