Permit Number: TC-COM-1123-02600
Parcel: 133369690

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1123-02600
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2023 Commercial Electrical APPROVED
11/17/2023 Site Zoning APPROVED
12/06/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
12/01/2023 Commercial Structural REQUIRES RESUBMIT Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Please provide the detail drawing for the 3 new 6 x 6 columns showing the footing.
2. Please provide the detail drawing for the new column top, box beam & existing 3 ft wall above ceiling.
3. Locate and label the water fountain on the floor plan.
4. Locate and label the mop sink on the floor plan.
5. Your code analysis mentions fire sprinkler is existing. Please re-confirm this & confirm if fire alarm exists as well.
6. Provide the drawings for the POS counter depicting the location of the handicap accessible counter with the required height and counter width.
7. Since 2 spaces are being combined, please confirm that you have made the adjustment on the address.
8. Since 2 spaces are being combined, please confirm that 2 electrical panel will remain and will be used as is and please coordinate with TEP how they would like this to be handled (provide their answer with your response please).
9. Since 2 spaces are being combined, please confirm that 2 HVAC units will remain and will be used as is and confirm that re-balancing will be done.
10. Please resubmit.
11/22/2023 Fire New Construction REVIEW COMPLETED
11/09/2023 PDSD Application Completeness REVIEW COMPLETED