Permit Number: TC-COM-1123-02577
Parcel: 11917038E

Address:
3700 S 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.5

Permit Number - TC-COM-1123-02577
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/24/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Not all the previous plan review comments were addressed, or insufficient information was re-submitted. Please review the comments and address completely.

1 The Original plan review Comment #4 is still not complete. Provide lumen calculations for both Fully Shielded and Un-Shielded.

2 The original Comment #5 (special Inspection) not addressed.

3 I will provide an attachment with an email reply to Mary Ann Collins. I’m not sure who this person is. I assume per the email this person is associated with this project. If utilized this template should help with the lumen calculations and other requirements.

Ref;2018 IBC section 107.2.1, 2012 City of Tucson Outdoor Lighting Code.
04/23/2024 PDSD Application Completeness REVIEW COMPLETED