Permit Number: TC-COM-1123-02575
Parcel: 134180100

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1123-02575
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/10/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved with Comments
Reason:
Date Completed : 11/30/2023 11:58:50 PM
No structural changes were included in the proposed work.



Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved with Comments
Reason:
Date Completed : 4/9/2024 8:07:32 PM
Approved as shown however if the plumbing approval require reconfiguration of the bathroom spaces, the building, electrical and HVAC will need to be re-reviewed for the revised floor plans.



Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 4/9/2024 8:02:50 PM




Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 4/9/2024 8:02:38 PM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 4/9/2024 2:33:12 PM
Second Plumbing Review:
Pending Bldg review: 1). Need to address Bldg plan review comments 2,5,7,9,10,11 -IPC 403.1, 404.2

Unresolved: 2). GENERAL: This Occupancy type & load requires 2 ADA compliant restrooms - IPC 403.1, 404.1, 404.2 update all affected pages.

Unresolved 3). General: Access to the 2nd required rest room can't pass thru kitchens or storage rooms update all affected pages -IPC 403.3.1

RESOLVED 4). Hose bibs on Plan page P1..2 need individual shut off valves -IPC 606.23). GENERAL: Access to the 2nd required rest room can't pass thru kitchens or storage rooms update all affected pages -IPC 403.3.1
04/04/2024 PDSD Application Completeness Express REVIEW COMPLETED