Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1122-00199
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/03/2023 | Commercial Building | APPROVED | |||
12/14/2022 | Site Zoning | APPROVED | |||
01/03/2023 | Site Engineering | NOT REQUIRED | |||
01/03/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/14/2022 | Commercial Electrical | REQUIRES RESUBMIT | 1.Verify that the system service disconnect switch is rated for the available fault current and Suitable for use as Service Equipment. NEC 690.13(C). 2.Indicate the equipment being utilized as the Rapid Shutdown Initiation Device and attach the appropriate label. NEC 690.12(C). Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
12/28/2022 | Fire New Construction | REQUIRES RESUBMIT | Provide perimeter pathways in accordance with IFC 2018, 1204.3. Please reach out if you have any questions. Patricia Shelton Patricia.shelton@tucsonaz.gov 520.837.7082 |
||
12/09/2022 | PDSD Application Completeness | REVIEW COMPLETED |