Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-1122-00199
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/21/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/21/2023 | Commercial Electrical | REQUIRES RESUBMIT | Previous plan review comment not addressed; "2.Indicate the equipment being utilized as the Rapid Shutdown Initiation Device and attach the appropriate label (35) . NEC 690.12(C). Ref; 2018 IBC section 107.2.1, 2017 NEC" The Line diagram shows label #35 applied to the ‘Existing 1200A Buss Gutter’ ? How can that be utilized as a ‘Rapid Shutdown Initiation Device’? |
||
02/06/2023 | Fire New Construction | REVIEW COMPLETED |