Permit Number: TC-COM-1122-00199
Parcel: 10709070D

Address:
500 W GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1122-00199
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/21/2023 Commercial Electrical REQUIRES RESUBMIT Previous plan review comment not addressed;

"2.Indicate the equipment being utilized as the Rapid Shutdown Initiation Device and attach the appropriate label (35) . NEC 690.12(C). Ref; 2018 IBC section 107.2.1, 2017 NEC"

The Line diagram shows label #35 applied to the ‘Existing 1200A Buss Gutter’ ? How can that be utilized as a ‘Rapid Shutdown Initiation Device’?
02/06/2023 Fire New Construction REVIEW COMPLETED