Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1122-00197
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/14/2022 | Site Zoning | APPROVED | |||
| 01/03/2023 | Site Engineering | NOT REQUIRED | |||
| 02/13/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/13/2023 | Commercial Building | REQUIRES RESUBMIT | 1) Provide structural analysis of roof system indicating structure has capacity for added load of solar panels and mounting meets required design criteria per 2018 IBC. | ||
| 12/13/2022 | Commercial Electrical | REQUIRES RESUBMIT | 1.The PV Array Equipment Grounding Conductors shall be connected to the Grounding Electrode System of the Building. Not at the Main Electrical Panel in the building. NEC 690.47. Per NEC art 250.24 requires the Building Grounding Electrode System to be connected by a Grounding Electrode Conductor to the Grounded Service Conductor(s) at the Service Disconnecting Means or at the Service Equipment. Show a code compliant Grounding Electrode System termination at the Service Equipment and continuous PV Array Equipment Grounding Conductor terminating at the Building Grounding Electrode System that complies with the above-mentioned code articles. Ref; 2018 IBC section 107.2.1, 2017 NEC arts 250, 690. |
||
| 01/05/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 12/09/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |