Permit Number: TC-COM-1122-00197
Parcel: 115051580

Address:
31 E RILLITO ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00197
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2022 Site Zoning APPROVED
01/03/2023 Site Engineering NOT REQUIRED
02/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/13/2023 Commercial Building REQUIRES RESUBMIT 1) Provide structural analysis of roof system indicating structure has capacity for added load of solar panels and mounting meets required design criteria per 2018 IBC.
12/13/2022 Commercial Electrical REQUIRES RESUBMIT 1.The PV Array Equipment Grounding Conductors shall be connected to the Grounding Electrode System of the Building. Not at the Main Electrical Panel in the building. NEC 690.47. Per NEC art 250.24 requires the Building Grounding Electrode System to be connected by a Grounding Electrode Conductor to the Grounded Service Conductor(s) at the Service Disconnecting Means or at the Service Equipment.

Show a code compliant Grounding Electrode System termination at the Service Equipment and continuous PV Array Equipment Grounding Conductor terminating at the Building Grounding Electrode System that complies with the above-mentioned code articles.

Ref; 2018 IBC section 107.2.1, 2017 NEC arts 250, 690.
01/05/2023 Fire New Construction REVIEW COMPLETED
12/09/2022 PDSD Application Completeness Express REVIEW COMPLETED