Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1122-00183
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/09/2022 | Site Zoning | APPROVED | |||
| 01/03/2023 | Site Engineering | NOT REQUIRED | |||
| 01/14/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/14/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-COM-1122-00183 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied 1. Sheet TS1: The occupant load factor for the business area is incorrect. Provide a correctly calculated occupant load in accordance with Table 1004.5. 2. Sheet TS1: Provide a detailed space by space occupant load calculation in accordance with Section 1004.3 that also clearly shows the waiting area or provide clarification on how the seats are permanently fixed. 3. Sheet TS1: No egress plans have been provided. Provide detailed egress plans. 4. Sheet TS1: It appears that there are multiple tenants within the building. Provide additional information regarding the adjacent tenant to ensure proper tenant separation. Additionally, show the entire building plan. MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
| 01/05/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 12/08/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |