Permit Number: TC-COM-1122-00177
Parcel: 141305140

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00177
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/10/2023 Commercial Building REQUIRES RESUBMIT 1) Identify 2018 IBC as the applicable code for this project.
2) Clarify proposed use and occupancy classification. R-2 occupancy applies to congregate living facilities (nontransient) with more than 16 occupants. R-3 or R-4 occupancy classification may be more appropriate.
3) Per IBC Section 420.4, this building will require an automatic sprinkler system.
4) Provide written response to all review comments.
01/04/2023 Fire New Construction REQUIRES RESUBMIT You have your occupancy listed as a R-2 a Boarding House non transient. Will you be housing students and or is this more of a congregate care/ assisted living facility. Please clarify if assisted Living you would be classified as a R-4 and you will need to provide us the condition. You will also need to install fire sprinklers with either occupancy. This note shall be added to your drawings.

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
12/12/2022 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review Section

PROJECT:
TC-COM-1122-00177
10629 E Avalon Park Station – R-1 RCP
Convert House to Boarding House (1st Review)

TRANSMITTAL: December 12, 2022

Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-1 zone (UDC 4.7.1). A Boarding House, Group Dwelling is not a permitted use in this zone (Table 4.8-2).

1. For Zoning purposes, the boarding house, as stated on you plan, is considered to be group dwelling and is not allowed in the R-1 Zone. Provide a use as defined within the UDC that is allowed in the zone or a rezoning will be required.


If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/08/2022 PDSD Application Completeness REVIEW COMPLETED