Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1122-00177
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/10/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/10/2023 | Commercial Building | REQUIRES RESUBMIT | 1) Identify 2018 IBC as the applicable code for this project. 2) Clarify proposed use and occupancy classification. R-2 occupancy applies to congregate living facilities (nontransient) with more than 16 occupants. R-3 or R-4 occupancy classification may be more appropriate. 3) Per IBC Section 420.4, this building will require an automatic sprinkler system. 4) Provide written response to all review comments. |
||
01/04/2023 | Fire New Construction | REQUIRES RESUBMIT | You have your occupancy listed as a R-2 a Boarding House non transient. Will you be housing students and or is this more of a congregate care/ assisted living facility. Please clarify if assisted Living you would be classified as a R-4 and you will need to provide us the condition. You will also need to install fire sprinklers with either occupancy. This note shall be added to your drawings. Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
12/12/2022 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review Section PROJECT: TC-COM-1122-00177 10629 E Avalon Park Station – R-1 RCP Convert House to Boarding House (1st Review) TRANSMITTAL: December 12, 2022 Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal. This site is located in the R-1 zone (UDC 4.7.1). A Boarding House, Group Dwelling is not a permitted use in this zone (Table 4.8-2). 1. For Zoning purposes, the boarding house, as stated on you plan, is considered to be group dwelling and is not allowed in the R-1 Zone. Provide a use as defined within the UDC that is allowed in the zone or a rezoning will be required. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
12/08/2022 | PDSD Application Completeness | REVIEW COMPLETED |