Permit Number: TC-COM-1122-00158
Parcel: 135052020

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1122-00158
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2023 Site Zoning APPROVED
01/26/2023 Site Engineering NOT REQUIRED
02/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/07/2023 Commercial Building REQUIRES RESUBMIT 1) Verify Occupancy Classification: Occupancy identified as R-3, however per 2018 IBC, R-4 occupancy is more appropriate. Please identify Condition 1 and or Condition 2 of R-4 occupancy.
2) Verify plumbing fixture calculation.
3) Please provide a written response to each review comment.

Juan Garcia
Juan.Garcia@tucaonaz.gov
01/24/2023 Fire New Construction REQUIRES RESUBMIT Occupancy listed as a R-3, however, it exceeds the numbers for assisted living/care and shall be a R-4 occupancy. We will need the owner to also identify if they are a Condition 1 and or Condition 2 R-4 occupancy.
Fire sprinkler permit T22FC00557 not completed and approved, this permit shall be closed and approved prior to approval of these plans for a COFO

Questions:
Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
01/06/2023 PDSD Application Completeness Express REVIEW COMPLETED