Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-1122-00154
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/16/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/16/2023 | Water Sterilization Report (Deferred Submittal) | REQUIRES RESUBMIT | Incomplete report: the report should contain the results of a bacteriological examination by a licensed testing laboratory of the water in the distribution system after the chlorine has been purged from the system. Reference: Section 610.1, IPC 2018 | ||
10/13/2023 | PDSD Application Completeness | REVIEW COMPLETED |