Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
10/16/2023 Water Sterilization Report (Deferred Submittal) REQUIRES RESUBMIT Incomplete report: the report should contain the results of a bacteriological examination by a licensed testing laboratory of the water in the distribution system after the chlorine has been purged from the system. Reference: Section 610.1, IPC 2018