Permit Number: TC-COM-1122-00149
Parcel: 11307087A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00149
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2023 Commercial Building APPROVED
12/12/2022 Site Zoning APPROVED
01/03/2023 Site Engineering NOT REQUIRED
02/06/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/06/2023 Commercial Electrical REQUIRES RESUBMIT Electric storage (50) gal type water heaters are considered a continuous load per NEC 422.13. See water heater specifications on plan sheet ‘P2’. The WH is rated at 28.8 amps x 125% = 36 amps, therefore requiring a 40 OCPD and # 8AWG Cu feeder conductors #10 equipment ground. Please revise this for the electrical panel schedule and water heater circuit, and load calculations.

Ref; 2018 IBC 107.2, 2017 NEC
02/06/2023 Commercial Plumbing REQUIRES RESUBMIT The water calculations appear to note the installation of a new reduced pressure backflow prevention assembly but the size is unknown (X” RPBP).
Clarify what is being installed. Reference: Section 107.2.1, IBC 2018.
01/04/2023 Fire New Construction REVIEW COMPLETED
12/08/2022 PDSD Application Completeness Express REVIEW COMPLETED