Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/27/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00147

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
1. Sheet 6 Roof Framing Plan: Indicate bracing to be provided between trusses.
2. Sheet 6 Roof Framing Plan: Structural calculations for prefabricated members to be submitted prior to rough framing inspection and a copy kept on site. Add a note to this effect.


BUILDING REVIEW COMMENTS:
DENIED
Sheet 1 Building Code Analysis: Occupancy has been calculated incorrectly. The area of the Multipurpose Room is approximately 755 sf. No tables or chairs are shown, and presumably in some instances the room may be standing only or chairs only. The correct divisor for standing space is 5 net, and the legal occupancy of the Multipurpose Room is approximately 151 persons. If tables and chairs were shown, using a divisor of 15 net th e occupancy of the room would still be 51 persons and the occupancy of the building 52 persons. The correct occupancy classification is A-3 Community Hall. Please revise the Building Code Analysis.
Sheet 1 Plan: Plumbing fixtures are required for Assembly occupancy. Separate facilities are required for each sex. (IPC 403.2) None of the listed exceptions apply. Please revise the plan to provide two separate toilet rooms. Provide minimum fixtures required as listed in IPC Table 403.1.
Sheet 1 toilet room plan: Shelving in the toilet room may not impinge on the clear floor area required for forward approach to the sink conforming to ADA 305. Show and dimension the clear floor space for forward approach for each accessible fixture on the revised floor plan.
Sheet 1 Toilet Room Plan: Access to the urinal stall and the toilet stall does not meet accessibility requirements. Revise door arrangement to avoid passing through one stall to reach another. Revise to provide compartments and compartment doors that meet ADA 604.8 requirements.
Sheet 2 Sections C-C and D-D: R-20 batt insulation required in wood framed walls. (IEEC Table C402.1.3.) Please revise at each location shown.
Sheet 4 Section A-A: R-20 vs. R-19 batt insulation required in wood framed walls. (IEEC Table C402.1.3.) Please revise at each location shown.


MECHANICAL REVIEW COMMENTS:
DENIED
1. Sheets M1 and M2: Revise to provide heating and ventilation at two toilet rooms per architectural revisions


ELECTRICAL REVIEW COMMENTS
DENIED
Sheet E1: Revise Power Plan and Lighting Plan to provide two toilet rooms per architectural revisions.
Sheet E1 Lighting Plan: Ceiling suspended (paddle) fans shall be supported independently of an outlet box or by a listed outlet box or listed outlet box system conforming to the requirements of NEC Section 422.18. Add a note to this effect on the plan.
Sheet E2: Revise panel schedules to provide power and lighting to two toilet rooms


PLUMBING REVIEW COMMENTS:
DENIED
1. Sheets P1, P2, and P3: Revise plans and riser diagrams to provide two toilet rooms per architectural revisions.



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/28/2022 Site Engineering REQUIRES RESUBMIT See Zoning Comment
12/08/2022 Site Zoning REQUIRES RESUBMIT UNTIL DP21-0324 IS APPROVED BY ALL REVIEW AGENCIES ZONING CANNOT APPROVE THIS PLAN
01/03/2023 Fire New Construction REVIEW COMPLETED
12/05/2022 PDSD Application Completeness Express REVIEW COMPLETED