Permit Number: TC-COM-1122-00146
Parcel: 10821328B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00146
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2022 Site Zoning APPROVED
12/13/2022 Site Engineering NOT REQUIRED
12/27/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
12/22/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00146

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
APPROVED


BUILDING REVIEW COMMENTS:
DENIED
1. Sheet A1.1: This sheet indicates more than a business use it contains mix use. It includes a café (A-2) and a large training room (A-3). This has not been considered into the code analysis. Provide a complete and thorough code analysis in accordance with Section 1004.53.
2. Sheet A1.1: The occupant load calculations are incorrect. The first floor contains assembly spaces that have not been accounted for. A space by space occupant load calculation must be completed in accordance with Section 1004.3. Provide a complete occupant load calculation. Additionally, update the plumbing fixture calculations as necessary.
3. Sheet A1.1: The egress plans are incomplete. They do not contain the location of furniture, the travel paths from the most remote points and the distance of that travel path, etc. Provide a thorough and detailed egress plan in accordance with Chapter 10 of the IBC.
4. Sheet A1.1: The travel paths do not indicate the travel to an exit but to exit access. Travel distance must be measure to an exit in accordance with Section 1017.
5. Sheet A1.1: Provide clarification on the adjacent tenant on the first floor to ensure proper separation between tenants.
6. Sheet A1.1: Provide a detailed narrative as to the items being served and cooked in the café as additional requirement may be applicable.


MECHANICAL REVIEW COMMENTS:
DENIED
1. Provide additional details regarding the cooking operations in the café as vent hoods may be required.


ELECTRICAL REVIEW COMMENTS
DENIED
1. Sheet E3.0: Additional exit lighting required in the assembly areas. Provide additional exit lighting in accordance with Section 1013.
2. Sheet E3.0: The additional egress illumination is required. Provide additional egress illumination in accordance with Section 1008.
3. General: Provide an existing one line diagram.


PLUMBING REVIEW COMMENTS:
APPROVED


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/27/2022 Fire New Construction REQUIRES RESUBMIT
11/30/2022 PDSD Application Completeness REVIEW COMPLETED