Permit Number: TC-COM-1122-00146
Parcel: 10821328B

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.6

Permit Number - TC-COM-1122-00146
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.6
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/07/2024 Water Sterilization Report (Deferred Submittal) REQUIRES RESUBMIT The submitted report does not meet the reporting requirements of Section 610.1, IPC 2018. A report of the microbiological examination (e.g. Total coliform bacteria and E coli) is required. [Initial comment: The required water disinfection report is not an analysis of the inorganic chemicals in the water. Section 610.1 of the 2018 International Plumbing Code describes the testing requirements. Your report should contain a narrative of what water distribution system was tested and the method used to disinfect the water distribution system and the report of the bacteriological examination by a licensed testing laboratory.]
02/06/2024 PDSD Application Completeness REVIEW COMPLETED