Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.6
Permit Number - TC-COM-1122-00146
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.6
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/07/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/07/2024 | Water Sterilization Report (Deferred Submittal) | REQUIRES RESUBMIT | The submitted report does not meet the reporting requirements of Section 610.1, IPC 2018. A report of the microbiological examination (e.g. Total coliform bacteria and E coli) is required. [Initial comment: The required water disinfection report is not an analysis of the inorganic chemicals in the water. Section 610.1 of the 2018 International Plumbing Code describes the testing requirements. Your report should contain a narrative of what water distribution system was tested and the method used to disinfect the water distribution system and the report of the bacteriological examination by a licensed testing laboratory.] | ||
02/06/2024 | PDSD Application Completeness | REVIEW COMPLETED |