Permit Number: TC-COM-1122-00146
Parcel: 10821328B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1122-00146
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/20/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00146


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
APPROVED


BUILDING REVIEW COMMENTS:
DENIED
1. Sheet A1.1: The large break room would still be considered an assembly space and must be calculated as such. Provide an updated occupant load calculation for the break room.
2. Sheet A1.1: The egress plans are incomplete. They do not contain the location of furniture, the travel paths from the most remote points and the distance of that travel path, etc. Provide a thorough and detailed egress plan in accordance with Chapter 10 of the IBC. NOT COMPLIED
NOTE: It is important to indicate the location of proposed furniture to ensure proper occupant load calculations, travel distances, etc. Provide proposed furniture layouts.


MECHANICAL REVIEW COMMENTS:
APPROVED


ELECTRICAL REVIEW COMMENTS
APPROVED


PLUMBING REVIEW COMMENTS:
APPROVED


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/11/2023 Fire New Construction REVIEW COMPLETED
01/10/2023 PDSD Application Completeness REVIEW COMPLETED