Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.5
Permit Number - TC-COM-1122-00146
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.5
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/22/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/22/2024 | Water Sterilization Report (Deferred Submittal) | REQUIRES RESUBMIT | The submitted report does not meet the reporting requirements of Section 610.1, IPC 2018. The lab report is to determine the total coliform bacteria and E. coli bacteria in the water sample, not the concentration of chlorine in the water sample. | ||
01/22/2024 | PDSD Application Completeness | REVIEW COMPLETED |