Permit Number: TC-COM-1122-00121
Parcel: 11917038E

Address:
3700 S 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00121
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/22/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
12/22/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00121

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
1. In the architectural drawing notes, it states that the exterior walls are to be stripped down to the stud and insulation level, this would trigger a lateral analysis based on wind/ seismic whichever controls the design and based on the analysis, shear panels would need to be provided and shown on the drawing.
2. In the structural drawings for the roof framing, there is detail provided for strengthening of roof framing members but no supporting calculations are provided for the structural evaluation of existing roof framing for RTU loads and the required structural strengthening of roof members.


BUILDING REVIEW COMMENTS:
DENIED
1. Sheet A103 and A303: It appears that rain water will drain behind the concrete wall with no way to drain to a proper location. Roof drainage sizing calculations have not been provided. Provide roof drain sizing calculations to the roof plan in accordance with Section IPC 1106.1 & 1106.2
2. Sheet A103 and A303: GPM discharge amounts have not been provided for the roof/drain overflows. Provide the roof/drain overflows in accordance with Section IPC 1106.2.


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
CONDITIONALLY APPROVED
E100 POWER PLAN:
Duplicate Sheet Note #22 with conflicting directions. Correct or combine as required.
Sheet Note #9 is used.
E102 LIGHTING PLAN ELECTRICAL: Could not locate Sheet Notes 4 and 7.
E601 ELECTRICAL PANEL SCHEDULES: May want to upsize CB/conductor for oven tag #20032


PLUMBING REVIEW COMMENTS:
DENIED
First Plumbing Review:
1). Add primary roof drain & overflow roof drain detail to plan page A504 or A505 -IPC 1105, 1108
2). Add backflow device to espresso & coffee notes #9 & #10 on plan page P101 -IPC 608.17.1
3). Plumbing Fixture Schedule on plan page P001 needs to include Manufacturer names & Model Numbers. or provide Spec Manual- IPC 303
4). Add existing grease interceptor info & sizing calculations to the plumbing pages to show it is sized for this facility - IPC 1003.3.5, 1003.3.5
5). Add piping material specs for sanitary storm, water & gas to plan page P001 or provide spec manual - IPC 106.3.1
6). Ice machines on plan pages P102 & P502 can't discharge to the grease system -IPC 1003.2
7). As shown on plan page A103, the Plumbing Plan pages need to include info & illustrations of the new primary & secondary roof drains, conductors, sizing calculations. -IPC 1105, 1106.1, 1106.2, 1108
8). The water heater model number on plan page P001 doesn't correlate with the use of a concentric venting & combustion air piping system as shown on plan page M501- Add the correct water heater or exhaust & combustion air method to the mechanical & plumbing pages. -IFGC 304 & 503.1



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/15/2022 Site Engineering REQUIRES RESUBMIT See Zoning Comment
11/28/2022 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section



PROJECT: TC-COM-1122-00121

Starbucks (1st Review)

3700 S 6th Ave – C-2



TRANSMITTAL DATE: November 28, 2022



COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



This site is located in C-2 Zone (UDC 4.7.21). Food Service is a permitted use (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P.



As Development Package (DP), TD-DEV-1122-00034, has not had its 1st review completed, Zoning is not able to compare the building plans with the DP. Until the DP is approved Zoning cannot approve this building permit.



The DP sheets provided in the building plans either need to be the stamped approved DP plan, stamped for reference only or removed from the plan set.



If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.