Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1122-00103
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/01/2022 | Commercial Electrical | APPROVED | |||
01/30/2023 | Commercial Structural | APPROVED | |||
11/28/2022 | Site Zoning | APPROVED | |||
12/09/2022 | Site Engineering | NOT REQUIRED | |||
01/30/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/03/2023 | Commercial Mechanical | REQUIRES RESUBMIT | Footnote b on Table 403.3.1.1, IMC 2018 states that mechanical exhaust is required for the beauty salon and no air from the salon may be recirculated to any other space. FC-1 appears to be recirculating air from the salon area (335 square feet) to the remaining 728 square feet of the suite. Reference: Section 403.2.1 (3), IMC 2018. | ||
01/03/2023 | Commercial Plumbing | REQUIRES RESUBMIT | Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018. | ||
12/22/2022 | Fire New Construction | REVIEW COMPLETED | |||
11/23/2022 | PDSD Application Completeness | REVIEW COMPLETED |