Permit Number: TC-COM-1122-00100
Parcel: 11450004K

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1122-00100
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2023 Commercial Plumbing REQUIRES RESUBMIT 1. An un-approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide a civil plan showing the demolition of the existing septic system and the installation of the building sewer. Reference: Sections 107.2.1 and 107.2.6, IBC 2018.
2. The rim elevation of the next upstream sanitary manhole (8716-08, 2508.52’) is less than 12” below the first floor elevation of the existing building (2509.50’) and the first floor elevation of the proposed building (2509.45’). Provide backwater valves per Section 714.1, IPC 2018, as amended by the City of Tucson.
11/22/2022 PDSD Application Completeness Express REVIEW COMPLETED