Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1122-00095
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/23/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/23/2022 | Commercial Structural | REQUIRES RESUBMIT | 1. General: Provide written responses to all review comments 2. Sheet 1/1: Identify 2018 IBC as prevailing building code per section 107, 2018 IBC. 3. Sheet 1/1: Provide sizing of all members to be replaced. (posts and beams) 4. Sheet 1/1: Identify patch material type and application for repair of composite concrete. |
||
| 11/22/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |