Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/29/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Coordinate the odor control plan with the mechanical design. The odor control plan calls for continuous circulation of the air through activated carbon filters in a closed loop within each room while the mechanical design and the response letter both state that the activated carbon filter fans will be exhausting air from the rooms on a time schedule determined by the facility owner. The mechanical design does not clarify how the environmental sensors for CO2 are to accomplish any control over the CO2 concentration in each grow room.
2. The Trim & Package, the Dry, and the Pre-Roll room appear to have no provision for odor control.
09/19/2023 Site Zoning REQUIRES RESUBMIT FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: TC-COM-1122-00074 – Marijuana Dispensary Off-Site Cultivation Location
Tenant Improvement (1st Review)
546 E 25th St

TRANSMITTAL DATE: September 19, 2023
DUE DATE: September 22, 2023

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Comply with Commercial Mechanical Review comment. Demonstrate compliance with 4.9.9.E.2.k. Provide an Odor Mitigation plan for Zoning to review in collaboration with Commercial Mechanical. The Odor Mitigation Plan should demonstrate devices and techniques to be incorporated to mitigate odors and may be done through exhaust air filtration system with odor control that prevents internal odors from being emitted externally or through any other best practices deemed adequate for odor mitigation. Upon receipt of a formal complaint through code enforcement related to the marijuana facility’s odor, an inspection for compliance with the Odor Mitigation Plan will be conducted.

If you have any questions about this transmittal, Contact Loran Shamis at 520-837-2242 or by email Loran.Shamis@tucsonaz.gov
09/01/2023 Fire New Construction REVIEW COMPLETED
08/23/2023 PDSD Application Completeness Express REVIEW COMPLETED