Permit Number: TC-COM-1122-00073
Parcel: 11301146Z

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1122-00073
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/15/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00073

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 12/9/2022 12:59:53 AM

Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 6/15/2023 12:38:56 AM

Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 12/9/2022 12:59:41 AM

Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 6/15/2023 12:40:51 AM
1. Provide an interior lighting COMcheck or other approved methodology for the project for the new proposed lighting that is in compliance with the 2018 IECC. Response: No new lighting has been added to the project, all electrical are existing.
Comment: The plans indicate that the existing lighting is being changed to new fixtures. For existing buildings per 2018 C503.6 new lighting systems that are part of the alteration shall comply with section C405 unless the alterations replace less than 10 percent of the luminaries in a space. It appears that more than 10 percent of the buildings existing lighting fixtures are being replaced with new lighting fixtures and therefore must comply with the energy requirements. There is also new lighting shown in the dining room above the tables and a few new wall wash can light fixtures A-2 that are additional to what was indicated on the demo plan. Provide an interior lighting allowance in accordance with one of the methods in C405.3.2.
1. Clarify if the new lighting installed in the bathrooms will be switched by occupancy sensors, or if an alternate method will be installed for the switching of the lights. 2018 IECC C405.2.1. Response: No new lighting has been added to the project, all electrical are existing and relocated.
Comment: The plans indicate the existing florescent lighting is being replaced with new recessed can lighting in different locations such as above the vanities. The new lighting fixtures are required to follow the switching in accordance with the 2018 IECC C405.2.1. (See comment 1 above).
1. Indicate the location of all “night lighting” on the plans for egress illumination or indicate light sensors will be used. All rooms and usable floor surfaces in a building shall be equipped with artificial lighting and shall be illuminated at all times that the space is occupied. 2018 IBC 1008.2. Response: Night lighting has been added, see Sheet A1.2.
Comment: The new lighting fixtures to be on the night lighting circuit were not found on sheet A1.2. Please clearly mark these fixtures.
06/09/2023 PDSD Application Completeness REVIEW COMPLETED