Permit Number: TC-COM-1122-00071
Parcel: 134102350

Address:
400 S SARNOFF DR

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1122-00071
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2023 Site Engineering APPROVED
04/28/2023 Site Zoning APPROVED
05/01/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/17/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00071

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
Tensioned fabric shade structure shall be provided in a deferred submittal


BUILDING REVIEW COMMENTS:
Denied
The electronic submittal contains both the revised set of drawings and the original set of drawings. Remove the original sheets and provide one full set of only revised drawings for approval stamps.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
No mechanical work has been included in this submitta


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Second Plumbing Review: Comments 3 & 4 still Remain
1). OK
2). OK-These restroom also serve the pools, PIMA county pool code requires a Urinal in mens restroom to remain. update plan page P-111 & all other affected pages. PIMA code 8.32.210**existing Restrooms on site near pool, Required Fixtures Subject To Field Inspections**
3). OK - Pima pool code requires showers. Update P-111 & all other affected pages -PIMA code 8.32.210 ** **existing Restrooms on site near pool, Required Fixtures Subject To Field Inspections**
4). New High/low drinking fountain now shown on plan page L-2, provide local authority approval allowing Drinking Fountain to discharge to earth as shown. Plumbing Code does not have an exception for this see -IPC 301.3
5). SAME-Show the required hot water source on plan page P-111 -IPC 607.1
6). OK



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/05/2023 PDSD Application Completeness Express REVIEW COMPLETED