Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/14/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00071


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
Tensioned fabric shade structure shall be provided in a deferred submitta

BUILDING REVIEW COMMENTS:
DENIED
1. Indicate on the drawings that all work will be done in accordance with the adopted codes of the City of Tucson, Pima County and the State of Arizona.
2. Provide expiration dates for the Landscape Architect Scott Martinez and the Registered Architect Daniel Maher as part of their State of Arizona stamp and seal.
3. Indicate a use group per the 2018 International Building Code on the drawings as well the construction type of the existing bathroom/ storage structure. Indicate the approximate square footage of construction on the drawings.
4. Provide and occupancy count for the new enclosed splash park area per IBC section 1004 and verify that one exit is sufficient for the area. Clarify if the paved area between the new ramp and the existing structure will be an egress route, it appears that the gate will interfere with the exiting.
5. Provide a section through the splash pad at the accessible ramp, retailing wall and adjacent pavement. Details are provided for the individual elements however the only section indicated was cut through the other direction.
6. Indicate the direction of water runoff for the shade canopies on the drawings. This would include water runoff to the existing diving pool. Roofs or canopies over pools and spas shall be provided in accordance with the IBC and shall be constructed so as to prevent water runoff into the pool or spa. It is unknown if the runoff will reach the existing dive pool. 2018 IPSC 307.1.3.
7. Sheet A111 and G-5 indicates that the existing storage and pump areas are not in the scope of work for this project although the plans indicate the new equipment will be located in this storage area remove or revise the notes from this sheet.
8. Indicate a wheelchair accessible table on the new deck area, the four tables shown appear to have fixed seating spaced in a way that would not allow approach by a wheelchair and no alternative tables were found. ANSI 901.1.
9. Indicate the location of the designated accessible parking spaces on the site plan sheet G-5.
10. The new restroom doors on sheet A111 do not appear to have a minimum of 12” on the push side of the door at the latch. Modify the restrooms to meet this clearance. ANSI figure 404.2.3.2.
11. Clarify the overall depth of the new electric hand driers mounted on the wall of the renovated restrooms, it appears they may extend into the door clearance. ANSI figure 404.2.3.2.


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
No mechanical work has been included in this submittal


ELECTRICAL REVIEW COMMENTS
DENIED
1. The splash pad equipment room plans on sheet SP-901 and ES201 do not show the minimum 30” wide clearance for the electrical panel and controls. Verify that both the panels provide the minimum working clearance. 2017 NEC 110.26.
2. Indicate the electrical lighting and switches in the equipment rooms, it is unknown if there is existing lighting to remain or if new lighting will need to be installed.
3. Clarify if the new lighting installed in the bathrooms will be switched by occupancy sensors. 2018 IECC C405.2.1


PLUMBING REVIEW COMMENTS:
DENIED
First Plumbing Review:
1). Need to address building plan review occupancy comment #4 to determine plumbing fixture count. -IPC 403.1
2). These restroom also serve the pools, PIMA county pool code requires a Urinal in mens restroom to remain. update plan page P-111 & all other affected pages. PIMA code 8.32.210
3). Pima pool code requires showers. Update P-111 & all other affected pages -PIMA code 8.32.210
4). Plan page P-111 drinking fountain can't be removed, needs to High/Low type. -IPC 403.1, 410.3
5). Show the required hot water source on plan page P-111 -IPC 607.1
6). lavatories on plan page P-111 need ASSE 1070 mixing valves -IPC 419.5


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/06/2022 Site Engineering REQUIRES RESUBMIT See Zoning Comment
11/22/2022 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL



FROM: PDSD Zoning Review



PROJECT: TC-COM-1122-00071 – TD-DEV-1122-00024

400 S Sarnoff Dr. - R-1

New Splash Pad – (1st Review)



TRANSMITTAL: November 22, 2022



This site is located in R-1 Zone (UDC Article 4.7.8).



As TD-DEV-1122-00024 has not completed the first review Zoning is not able to compare the building plans to the DP. Once the 1st review of the DP is completed and comments addressed Zoning will review the building plans for compliance with the DP. Additional comments maybe forth coming. Zoning cannot approve the building plans until the DP is approved by all review agencies.



If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/26/2022 Fire New Construction REVIEW COMPLETED
11/18/2022 PDSD Application Completeness Express REVIEW COMPLETED