Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00063
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2022 Site Zoning APPROVED
12/23/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
12/23/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00063

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
1. The engineer professional stamp on the structural sheets indicates that Anthony Polusny is a Civil not a structural engineer. Provide a stamp and seal from a structural engineer on the structural drawings and include the seals expiration date.


BUILDING REVIEW COMMENTS:
DENIED
1. Provide the expiration date for the Registered Architect's license on the stamp on the drawings, only the date that the drawings were sealed was provided.


MECHANICAL REVIEW COMMENTS:
APPROVED


ELECTRICAL REVIEW COMMENTS
APPROVED


PLUMBING REVIEW COMMENTS:
APPROVED


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/06/2022 Site Engineering REQUIRES RESUBMIT Project: TC-COM-1122-00063

Address: 6377 E TANQUE VERDE RD

This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.)

Please start a new FUP at our permit application web page:

https://tdc-online.tucsonaz.gov/#/home

NOTE: Documentation of a cost estimate from your contractor will be required if this project involves any reconstruction, repair, rehabilitation, structurally connected addition, or other improvement of an existing structure (including TI’s and solar). Construction of separate builds/new structures does not require a cost estimate to be provided.

Instructions:

1. Navigate into the current project in the “My Work” tab. Within the permit, navigate to the “Sub-Records” tab and click “Apply” on the Floodplain Use Permit Sub-Record

2. Locations -> Confirm the location is accurate to the project. Click “Next”

3. Type -> Fill in the “Square Feet” and “Valuation” boxes with the project area and a contractor-provided cost estimate (See note above: for new structures, input 0). Click “Next”

4. Contacts -> Confirm contacts and add any additional contacts if applicable. Click “Next”

5. More Info -> This will be filled in by the engineer assigned to your case, Click “Next”

6. Attachments -> Please attach the project plan, supporting documentation for the cost estimate (if applicable), and a drainage/hydrology report (if applicable). Click “Next”

7. Signature -> Read the statement and type your name. Sign your name below (You may Enable Type Signature to have the software sign for you.) Click “Next”

8. Review and Submit -> Review all information to ensure accuracy. Click “Submit”

Contact Scott Haseman at scott.haseman@tucsonaz.gov, Stephen Blood at Stephen.Blood@tucsonaz.gov, or Loren Makus at Loren.Makus@tucsonaz.gov if you have any questions about the FUP.
12/19/2022 Fire New Construction REVIEW COMPLETED
11/16/2022 PDSD Application Completeness REVIEW COMPLETED