Permit Number: TC-COM-1122-00044
Parcel: 141185990

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00044
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2024 Site Engineering APPROVED
08/14/2024 Site Zoning APPROVED
08/15/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/31/2024 External Reviewers - Stantec REQUIRES RESUBMIT July 31, 2024
1st Review

Centennial American Properties
Attn: Jason Tankersley
1200 East Morehead, Suite 280
Charlotte, North Carolina 28204

Re: CAP STORAGE – OLD VAIL
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-1122-00044
Stantec Project Number: 185215066
Stantec File Number: TUC-24-096

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 105,504 240 Yes No
Separate Permits: Automatic fire sprinklers and signage.
Deferred Submittals: Metal stairs, storefront and window system, elevator shop drawings, prefabricated canopy
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, and masonry.

ARCHITECTURAL COMMENTS

Sheet A001

1. Please indicate on the cover page that the automatic fire sprinkler system [2018 IBC Sec. 903] is to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

2. The plans indicate that the metal stairs, storefront and window system, elevator shop drawings, and prefabricated canopy will be provided as part of deferred submittal. Either provide the documents now or list on this sheet as a deferred submittal and include the following notes:

PER IBC Section 107.3.4
<Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building.

PER IBC Section 107.3.4.1
Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building.

3. Note on the cover of the drawings that special inspection is required for earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, and masonry. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A100

1. The architectural site plan and Sheet C301 civil plan have conflicting square footages and building heights. Please coordinate and revise.

2. The site plan does not include the distances to property lines for the building. Please provide the distance from exterior walls to property line.


Sheet A102.1

1. Please add a wall type indicator to the elevator shafts.

Sheet A122

1. Please provide roof drain calculations for roof drain sizing. [Ref. IPC 2018 Sec. 1105.2]

Sheet A131

1. Please provide a detail and listed assembly for the 1-hour floor construction indicated. [Ref. IBC 2018 Sec. 703.3]

Sheet A500

1. Please indicate a minimum 1-hour rated fire door for doors ST1-2 and ST1-3. [Ref. IBC 2018 Sec. 716.1(2)]

Sheet A920

1. The Type M wall indicated has conflicting UL listed rated assemblies. The notes box indicates design based on UL No. U935, but the Rating section indicates UL U906. Please revise.

STRUCTURAL COMMENTS

General

1. The structural calculations provided do not include the foundation design calculations. Please provide the foundations calculations. [Ref. IBC 2018 Sec. 1604.4]

2. Please provide a statement of special inspections in accordance with Section 1704.3.1 of the 2018 International Building Code.

Sheet S120

1. The roof framing plan does not include the locations of the mechanical equipment and their additional load. Please revise and include.

Sheet S501

1. Detail 6 is missing the detail number and page reference for the hold-down at foundations. Please clarify and revise.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P101

1. The plan indicates that the building drain connection to the oil/water separator is included with the civil plan. The civil plan provided does not include the oil/water separator. Please coordinate and revise.


ELECTRICAL COMMENTS

General

1. Please provide on the plans complete outdoor lighting calculations showing compliance with the 2012 City of Tucson/Pima County Outdoor Lighting Code (OLC) on the plans which include the following information:
a. Each exterior luminaire type with the lumens for that type, the quantity of each type and whether the luminaire is full cut-off or unshielded, and the color rendition (i.e. not to exceed 3500K).
b. The total of full cut-off and unshielded lumens for the parcel.
c. A statement of the lighting area, the size of the permitted parcel, and the maximum allowed full cut-off and unshielded lumens.
d. A statement that special inspection is required (or is not required) per Sec. 104.2.2.
Also provide lighting fixture cut sheets for each exterior fixture.

2. Please provide an electrical site plan indicating the locations of all exterior lighting, underground electric service location, circuit designations, etc. Please be sure to provide an engineered foundation and calculations for light poles.

3. Please provide and energy conservation compliance report for exterior lighting. [Ref. IECC 2018 C402]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/15/2024 Fire New Construction REQUIRES RESUBMIT Address Stantec comments.
Questions: patricia.shelton@tucsonaz.gov
07/16/2024 PDSD Application Completeness Express REVIEW COMPLETED