Permit Number: TC-COM-1122-00044
Parcel: 141185990

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00044
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/19/2022 Fire New Construction REQUIRES RESUBMIT Comments:

You shall provide the following notes on sheet G1.0:
Fire sprinkler underground plans shall be submitted to and a permit obtained from TFD
Fire sprinkler plans shall be submitted to and a permit obtained from TFD
Fire alarm plans shall be submitted to and a permit obtained from TFD
Building shall be tested for ERRC by PCWIN and the report provided to TFD prior to the TCO
Elevator shall be compliant with the 2018 IBC, Chapter 30, Section 3001.2
Owner shall provide KNOX Elevator Key Box, KNOX key boxes and KNOX Locking F.D.C. caps
Owner shall provide elevator two-way communication

DP shall be approved prior to Building permit being completed.

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
12/02/2022 Site Engineering REQUIRES RESUBMIT Please include full site address on all documents.
11/17/2022 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL



FROM: PDSD Zoning Review



PROJECT:



TC-COM-1122-00044

No Address – I-1

Personal Storage (1st Review)



TRANSMITTAL: November 17, 2022

COMMENT: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed.



This site is located in I-1 Zone Zone (UDC 4.7.29). Personal Storage is a permitted use (UDC Table 4.8-5) subject to Use Specific Standards 4.9.10.C.3 & .6 and 4.9.13.Q.



As a development package has not yet been accepted for review for this proposed Personal Storage project Zoning is not able to review the building plans at this time. Once the 1st development package (DP) Zoning will review the building plans for compliance with the DP. Additional comments maybe forth coming.



If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
10/18/2023 External Reviewers - Stantec REVIEW COMPLETED
09/26/2023 PDSD Application Completeness Express REVIEW COMPLETED