Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/19/2022 | Commercial Mechanical | APPROVED | |||
12/19/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/17/2022 | Commercial Electrical | REQUIRES RESUBMIT | Provide complete electrical feeder/branch circuit information for the conductor, conduit runs and terminations between the SF-1 and SF-2 Power Panels and the junction boxes for the supply fans. Verify load and locate “Local to Remain Receptacle” (Per KEY NOTE #4, plan E1.1) on the power plans. Indicate branch circuit and panel. Indicate wiring methods or how the supply fans are wired and connected to the junction boxes. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC 2018 IECC, City of Tucson Commercial Plan /Permit Submittal Requirements. |
||
11/05/2022 | PDSD Application Completeness | REVIEW COMPLETED |