Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2022 Commercial Mechanical APPROVED
12/19/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/17/2022 Commercial Electrical REQUIRES RESUBMIT Provide complete electrical feeder/branch circuit information for the conductor, conduit runs and terminations between the SF-1 and SF-2 Power Panels and the junction boxes for the supply fans.

Verify load and locate “Local to Remain Receptacle” (Per KEY NOTE #4, plan E1.1) on the power plans. Indicate branch circuit and panel.

Indicate wiring methods or how the supply fans are wired and connected to the junction boxes.

Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC 2018 IECC, City of Tucson Commercial Plan /Permit Submittal Requirements.