Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1122-00025
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2022 | Site Zoning | APPROVED | |||
| 11/28/2022 | Site Engineering | NOT REQUIRED | |||
| 01/06/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/17/2022 | Commercial Electrical | REQUIRES RESUBMIT | Provide complete electrical plans for the power and lighting, Mechanical equipment and devices. Provide branch circuit, panel designations and correlate with the associated complete panel schedule. Identify all new electrical on the plans. Provide compliance the 2018 IECC for the lighting if applicable. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC 2018 IECC, City of Tucson Commercial Plan /Permit Submittal Requirements. |
||
| 12/20/2022 | Commercial Mechanical | REQUIRES RESUBMIT | Provide calculations to verify that adequate ventilation will be provided for the occupied spaces and the restrooms. Reference: Section 403.3.1.1, IMC 2018. | ||
| 12/20/2022 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have chemicals, cleaning agents, or other contaminants that may come in direct contact with water. Show the location of the reduced pressure backflow assembly and water meter on the drawings; indicate the size of both items. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf. 2. Revise the “piping axonometric” to reflect both the existing and proposed waste & vent piping. Label the fixtures and all of the pipe sizes. Note that the use of a horizontal wet vent is limited to bathroom groups only, in this case two water closets and two lavatories (see Section 912.1, IPC 2018). Reference: Section 107.32.1, IBC 2018. 3. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 4. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018. 5. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (i.e. 24” for ½” pipe). 6. Provide keynote #15. Reference: Section 107.2.1, IBC 2018. |
||
| 01/06/2023 | Commercial Structural | REQUIRES RESUBMIT | Review Comments: 1) Provide written responses to review comments. 2) Sheet A2.1: Verify and provide fully compliant dimensioning of the new ADA bathroom including grab bars, floor clearances, lavatories, signage, etc. 3) Sheet S2.0: Add reference to associated structural calculations related to the 5 1/2" x 16" GLB in the roof framing plan |
||
| 12/04/2022 | Fire New Construction | REVIEW COMPLETED | |||
| 11/05/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |