Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-1122-00025
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/18/2023 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The balance report is incomplete: see the Outside Air Ventilation Schedule for the minimum required supply air quantities for each room on sheet M1.0 and included in the submitted air balance report. Reference: Section 403.3.1.1, IMC 2018. | ||
| 09/15/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |