Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-1122-00023
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/16/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/16/2024 | Air Balancing/Commissioning Report (Deferred Submittal) | REQUIRES RESUBMIT | The drawings for TC-COM-1122-00023 call for whole house ventilation provided by exhaust fan EF-1. Provide an air balance report by a certified air balancing technician that demonstrates that the fan is operating as designed. Reference: Section 403.3.1.5, IMC 2018, as amended by the City of Tucson. | ||
07/10/2024 | PDSD Application Completeness | REVIEW COMPLETED |