Permit Number: TC-COM-1122-00016
Parcel: 103090800

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00016
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2022 Site Zoning APPROVED
11/28/2022 Site Engineering NOT REQUIRED
12/16/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
12/16/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00016

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
APPROVED


BUILDING REVIEW COMMENTS:
DENIED
1. Sheet G100: Provide a narrative on the processes and the items being manufactured. Additionally, provide information stored in the H-2 use. Ensure all requirements of Section 415 have been reviewed.
2. Sheet A102: Provide the location of all exit signage and egress illumination in accordance with Section 1008 and 1013.
3. Sheet A701: UL fire resistance rated assemblies typically are comprised of proprietary materials to achieve a complete assembly. Revise the entire assembly (UL U419) on this sheet to reflect the current assembly listed by UL. The current UL listed assembly is dated September 5, 2022.


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
APPROVED


PLUMBING REVIEW COMMENTS:
CONDITIONALLY APPROVED
First Plumbing Review: Ok Subject to field inspections



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/12/2022 Fire New Construction REQUIRES RESUBMIT Comment: You shall provide a written narrative letter of the operations in every area of the building all throughout and storage quantities in the H.
Provide a full Hazardous Material Inventory Statement (HMIS) Per IFC 2018, Chapter 50, Section 5001.5.2.
Provide MSDS and all quantities of chemicals being used throughout the buildings and define the operations in those areas.
Provide a Hazardous Material Management plan per the IFC 2018, Chapter 50 Section 5001.5.1

Questions:
Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
11/05/2022 PDSD Application Completeness REVIEW COMPLETED