Permit Number: TC-COM-1026-01784
Parcel: 12801007A

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1026-01784
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2026 Commercial Electrical Standard APPROVED
11/04/2026 Design Review Standard NOT REQUIRED Not in a Special District.
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Commercial Mechanical Standard PENDING ASSIGNMENT
N/A Commercial Plumbing Standard PENDING ASSIGNMENT
N/A Commercial Post Review Express PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
N/A Water - PDSD Standard PENDING ASSIGNMENT
11/19/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1026-01784 (5530 E BROADWAY BL TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The addition of the under-canopy lighting fixtures requires compliance with the adopted Outdoor Lighting Code.
2. Show the under-canopy lighting fixtures as full-cutoff as defined in chapter two of the outdoor lighting code, or provide complete lumen calculations for the site. OLC 401.2.1(3).
3. Show lighting fixtures with a Maximum color temperature of 3500K, OLC 402.1.
11/05/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-1026-01784 (1st Review)
Project: SAVERS Donation Drive Thru Canopy
Location: 5530 E BROADWAY BL
Review Date: 11/05/2026
Reviewer: John Mounsey – Engineering Associate
Reviewer Contact Information: john.mounsey@tucsonaz.gov

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering.
To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Submit your response letter and updated plan set as two separate files.

Site Engineering Comments:
Tucson’s Unified Development Code (UDC), Section 7.4.6.E.2, Height Clearance established a minimum height clearance of 15’ along access lanes and PAALs. Sheet A101.1 detail 5 shows a clearance of 14.5’. Please revise your plans to reflect the code requirement.

If you have any questions or concerns, please contact John Mounsey at John.Mounsey@tucsonaz.gov
11/04/2026 PDSD Application Completeness Express REVIEW COMPLETED