Permit Number: TC-COM-1026-01770
Parcel: 140260360

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1026-01770
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2026 Commercial Electrical Standard APPROVED
11/02/2026 Commercial Mechanical Standard APPROVED
11/02/2026 Commercial Plumbing Standard APPROVED
10/30/2026 Site Zoning Standard APPROVED
11/02/2026 Water - PDSD Standard APPROVED
11/02/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
10/30/2026 Site Engineering Standard NOT REQUIRED TI Only
11/04/2026 Commercial Post Review Express PENDING ASSIGNMENT
11/03/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit a complete set of revised/corrected documents and a written response addressing each review comment and explaining how it was resolved. The original submittal was incomplete, and additional comments may be issued upon subsequent review.
Please email me with any questions regarding the comments below. mark.masek@tucsonaz.gov
1. Please verify that all sheets display correctly, unused viewports are turned off, and no unintended layers or drawing elements appear in the final PDF set.
2. Please obtain an official suite address from Pima County Addressing before the next submittal. Include the assigned suite number on the cover sheet and in the title block on all drawings.
3. Please place these notes on the cover sheet with the name of the Registered Design Professional named and include contact information.
A. PER IBC Section 107.3.4
<Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building.
B. PER IBC Section 107.3.4.1
Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building.
4. Sheet A0.0: Please verify and amend the project location pointer to read 2700 E. Commerce Center Place on the Property Map or revise the address of this permit, as the current pointer appears to indicate a portion of 2700 E. Commerce Center Place.
5. Please see TC-COM-1124-02270 in https://pro.tucsonaz.gov/ to see the Suite 150 floor plan for a reference.
6.Sheet A0: Please provide the total square footage and total design load for this new suite. IBC 107.2.1,
7. Sheet A0.1: Please provide an exit and egress plan for the new suite only, in accordance with 2024 IBC Section 107.2.1. Dimension the total exit access travel distance on the plan, clearly identifying the starting and ending points. Show the maximum exit access travel distance from each cleanroom area to the applicable exit. For Group F-1 occupancy, identify the applicable maximum allowable travel distance of 250 feet in accordance with IBC Section 1017.2.8.
Sheet A0.1: Please show Exit signs on the Exit Egress plan and ensure they are consistent with the electrical lighting plans so all plans match. IBC 107.2.1


Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/04/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
10/29/2026 PDSD Application Completeness Express REVIEW COMPLETED