Permit Number: TC-COM-1026-01753
Parcel: 12511162C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1026-01753
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2026 Commercial Building Standard NOT REQUIRED
11/20/2026 Commercial Plumbing Standard NOT REQUIRED
11/10/2026 Fire New Construction Standard NOT REQUIRED
11/13/2026 Outdoor Lighting Standard NOT REQUIRED
11/02/2026 Site Engineering Standard NOT REQUIRED
11/18/2026 Site Zoning Standard NOT REQUIRED
11/20/2026 Water - PDSD Standard NOT REQUIRED
11/20/2026 Commercial Post Review Express PENDING ASSIGNMENT
11/13/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1026-01753 (919 N ALVERNON WY TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
2. Provide GFCI protection for each new HVAC unit per NEC 210.8(F). All outdoor OUTLETS require GFCI protection.
3. The Equipment Mini-split details on the line diagram do not match the details/specs shown in the Equipment Specifications provided. Provide consistent equipment information.
4. The line diagram shows two new panels, 'F' & 'G' being added for new apartments. This will require separate permits.
5. There are two panels labeled as ā€˜G’.
6. Provide conduit fill ampacity calculations for conduits from Panel 'G'. #10 cu conductors are undersized given the 30 current carrying conductors in each conduit from the panel.
7. Provide individual Equipment Grounding Conductors for each branch circuit. Notes on the conduits from Panel 'G' indicates that only one EGC is in the conduit.

Note, Each unit will require separate permits.
>>> Additional comments may be forthcoming with updated and Sealed plans.
11/20/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1026-01753
ADDRESS/PARCEL: 919 N ALVERNON WY TUCSON, AZ 85711

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please provide the specifications for the proposed new mini-split units on the plans. The units shall comply with Sections R403.7 and R501.4, IECC 2024 and shall comply with the Department of Energy efficiency requirements that went into effect on January 1, 2023.
2. Please provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
10/28/2026 PDSD Application Completeness Express REVIEW COMPLETED