Permit Number: TC-COM-1026-01751
Parcel: 128010520

Address:
110 S WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1026-01751
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2026 Site Zoning APPROVED
11/10/2026 Water - PDSD APPROVED
10/28/2026 Site Engineering NOT REQUIRED
11/12/2026 Commercial Post Review Express PENDING ASSIGNMENT
11/10/2026 Commercial Building REQUIRES RESUBMIT Please submit a complete set of revised/corrected documents and a written response addressing each review comment and explaining how it was resolved. The original submittal was incomplete, and additional comments may be issued upon subsequent review.
Please email me with any questions regarding the comments below: mark.masek@tucsonaz.gov
1. Please provide the structural calculations used in the design of the modifications to this structure. IBC 107.2.7
2. Please revise the sheet index and plan set to show all sheets included in this permit. Ensure each sheet has the correct and unique sheet number. IBC 107.2.1
For example:
Sheets A100, M5.0 & M5.1 are listed in the index but is missing from the plan set.
Sheet A300 is included in the plan set but is not listed in the sheet Index.
3. Sheet A300: The plans appear to indicate a door without a landing at the same level as the floor. IBC 1010.1.4 requires a landing at the same height on each side of the door. Please amend the plans to comply.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/05/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1026-01751 (110 S WILMOT RD TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The conductors to the following equipment are undersized for the given 35A OCPDs, CU-1, CU-2 & 303. OCPD(Breaker) for copper conductors may not exceed 30A for #10AWG conductors as required by NEC 240.4(D)(small conductors).
2. Provide GFCI for Kitchen Equipment #300, reach in freezer, NEC 210.8(B).
11/10/2026 Commercial Mechanical REQUIRES RESUBMIT Clarify the sequence of operation for EF-2. The exhaust fan schedule shows both, “fan to run continuously” and a “break-glass type switch labeled ‘ventilation system emergency on-only’”. Reference: Section 107.2.1, IBC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
11/10/2026 Commercial Plumbing REQUIRES RESUBMIT Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 604.4, IPC 2024, and Section 606.4, ICC/ANSI A117.1-17.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
11/12/2026 Fire New Construction REQUIRES RESUBMIT Resolve building review comments.
Please remove existing fire sprinkler and fire alarm from your submittal, unless you intend on providing them.
Questions: patricia.shelton@tucsonaz.gov
10/28/2026 PDSD Application Completeness Express REVIEW COMPLETED