Permit Number: TC-COM-1026-01739
Parcel: 13613001S

Review Status: In Review

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1026-01739
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2026 Commercial Electrical APPROVED Approved with notes added to plans:
Provide a GFCI [NEC 210.8(E)] receptacle outlet on the same level within 25’ of all HVAC units [NEC 210.63(B)(1)].
Provide GFCI receptacle within electrical equipment rooms, [NEC 210.8(E), 210.63(B)(2)]
11/05/2026 Site Zoning APPROVED
11/05/2026 Water - PDSD APPROVED
11/05/2026 Commercial Plumbing NOT REQUIRED
10/27/2026 Site Engineering NOT REQUIRED
N/A Commercial Building PENDING ASSIGNMENT
N/A Commercial Post Review Express PENDING ASSIGNMENT
N/A Fire New Construction PENDING ASSIGNMENT
11/05/2026 Commercial Mechanical REQUIRES RESUBMIT Provide cooling load calculations to justify the additional cooling capacity of the specified HVAC unit. Reference: Section C403.1.1 and C403.3.1, IECC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
10/27/2026 PDSD Application Completeness Express REVIEW COMPLETED