Permit Review Detail
Review Status: In Review
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1026-01739
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2026 | Commercial Electrical | APPROVED | Approved with notes added to plans: Provide a GFCI [NEC 210.8(E)] receptacle outlet on the same level within 25’ of all HVAC units [NEC 210.63(B)(1)]. Provide GFCI receptacle within electrical equipment rooms, [NEC 210.8(E), 210.63(B)(2)] |
||
| 11/05/2026 | Site Zoning | APPROVED | |||
| 11/05/2026 | Water - PDSD | APPROVED | |||
| 11/05/2026 | Commercial Plumbing | NOT REQUIRED | |||
| 10/27/2026 | Site Engineering | NOT REQUIRED | |||
| N/A | Commercial Building | PENDING ASSIGNMENT | |||
| N/A | Commercial Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Fire New Construction | PENDING ASSIGNMENT | |||
| 11/05/2026 | Commercial Mechanical | REQUIRES RESUBMIT | Provide cooling load calculations to justify the additional cooling capacity of the specified HVAC unit. Reference: Section C403.1.1 and C403.3.1, IECC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 10/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |