Permit Number: TC-COM-1026-01731
Parcel: 14108534A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1026-01731
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2026 Site Zoning Standard APPROVED
10/21/2026 Site Engineering Standard NOT REQUIRED
11/12/2026 Commercial Post Review Express PENDING ASSIGNMENT
11/12/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit a complete set of revised/corrected documents and a written response addressing each review comment and explaining how it was resolved. The original submittal was incomplete, and additional comments may be issued upon subsequent review.

Please email me with any questions regarding the comments below: mark.masek@tucsonaz.gov

1. Sheet CS-1: Please update the Building Code Analysis to reflect the 2024 IBC referenced standards 107.2.1 For example,
ANSI MH16.1-2021
"2021 RMI Rack Design Manual"
ASCE 7-22
2. Please provide the Seismic Design Category on the structural calcualtions and construction drawings. IBC 107.2.1


Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/12/2026 Fire New Construction Standard REVIEW COMPLETED
10/21/2026 PDSD Application Completeness Express REVIEW COMPLETED