Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1026-01730
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/21/2026 | Commercial Electrical Express | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1026-01730 (9525 E OLD SPANISH TR TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. The specification sheets for the CELLULAR COMMUNICATOR HWF2V-COM shows the need for a 120 VAC circuit. Clarify if there is an existing circuit available or if a new circuit is being run. 2. This scope of work also requires a separate fire alarm modification permit through the fire department. Please contact Tucson Fire for more information. |
||
| 10/21/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |