Permit Number: TC-COM-1026-01712
Parcel: 134180090

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1026-01712
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2026 Commercial Mechanical NOT REQUIRED
10/26/2026 Site Engineering NOT REQUIRED
11/04/2026 Site Zoning NOT REQUIRED
11/02/2026 Water - PDSD NOT REQUIRED
10/30/2026 Commercial Building REQUIRES RESUBMIT Please submit a complete set of revised/corrected documents and a written response addressing each review comment and explaining how it was resolved. Please note that the original submittal was incomplete, and the review was based on the information provided. Additional comments may be issued upon subsequent review.

Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete construction documents, plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2024 IBC section 107.1. , City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf

2. Please have an Arizona Registrant provide a damage report indicating that findings are comprehensive regarding the damage sustained by the structure(s). IBC 107.2.1
3. Provide a detailed description indication the scope of the project. IBC 105.1
4. Provide construction documents indicating where the damage occurred on the building. IBC 107.2.1
5. Provide construction documents showing the new construction in the damaged areas. IBC 107.2.1




Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/02/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1026-01712 (7340 E BROADWAY BL TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete construction documents, plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2024 IBC section 107.1. , City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf

2. Please have an Arizona Registrant provide a damage report indicating that findings are comprehensive regarding the damage sustained by the structure(s). IBC 107.2.1. Include, in the report, analysis and repairs required for the electrical systems, both inside and outside, due to the water damage and the tree falling on the outdoor electrical lines.
3. Provide a detailed description indication the scope of the project. IBC 105.1
11/02/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1026-01712
ADDRESS/PARCEL: 7340 E BROADWAY BL TUCSON, AZ 85710

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please provide the specifications and listing information for the proposed water heater. Reference: Sections 303.2 and 501.5, IPC 2024 and Section 107.2.1, IBC 2024.
2. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
11/06/2026 Fire New Construction REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
10/23/2026 PDSD Application Completeness Express REVIEW COMPLETED