Permit Number: TC-COM-1026-01706
Parcel: 141186740

Address:
8872 S RAIL PL

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1026-01706
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Commercial Electrical Standard PENDING ASSIGNMENT
N/A Commercial Mechanical Standard PENDING ASSIGNMENT
N/A Commercial Plumbing Standard PENDING ASSIGNMENT
N/A Commercial Post Review Express PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
N/A Water - PDSD Standard PENDING ASSIGNMENT
11/05/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1026-01706 (9748 E OLD VAIL RD TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different outdoor light sources on your lighting plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
a. Update the Outdoor lighting Lumen calculations on sheet SE-1. Calculations table shall include whether each fixture is full-cutoff (OLC 104.2), or unshielded. Show which fixtures are installed under canopies or overhangs (OLC401.2.1(3) & (4)).
b. Verify the correct Developed Area is being used to calculate the 'Total Allowed Lumens'. The Developed Area used should include only the portion of the site that is being developed under this permit. Portions that are to be developed in the future should be excluded from the Developed Area used for this permits. This is to ensure that area to be developed under future permits doesn't have it's lumen allowance used up on the early developments.
2. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
a. Show how the 'Total Allowed Lumens' was calculated. Provide the compliance option chosen from OLC Table 401.1. The total number appears incorrect per my review.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
a. The provided calculations are missing lighting fixtures, F, F2, L, X3.
b. Full-cutoff fixtures under canopies and overhangs are exempt from the total lumen calculations, but must be shown on the calculations and shown as exempt. OLC 401.2.1(3).
c. Show Lighting Fixture 'GA' in the provided 'Lighting Fixture Schedule' on sheet E1. Show lighting fixture as Full-cutoff, per OLC chapter 2 definition, with a Maximum color temperature, 3500K, OLC 402.1. Also show if this light is full-cutoff. The Fixture detail on sheet SE-1 seems to show an unshielded fixture.
4. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
a. Reference sheet E3, Plan Notes #12, Receiving/Loading Dock. Plan Note 12 indicates flood lights to be installed, but plans show fixture B2 installed. Fixture B2 doesn't appear to accept the GE #68182, PAR 38 lamps as indicated in Plan Note 12. Flood lights are typically unshielded/non-full-cutoff and must be shown within the lumen calculations. Detail how these lighting fixtures are used and include them in the Lighting Fixture schedule and lumen calculations as necessary.
5. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
a. Lighting Fixtures B, B1, B2, B2, F, F2, and L all show color temperatures of 4000K.
6. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
7. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

8. Specify any exceptions used.

9. Provide Curfew lighting controls If applicable Per section 403.
11/04/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-1026-01706 (1st Review)
Project: Vail Costco Warehouse
Location: 9748 E OLD VAIL RD
Review Date: 11/04/2026
Reviewer: John Mounsey – Engineering Associate
Reviewer Contact Information: john.mounsey@tucsonaz.gov

Site Engineering Comments:
1. Site Engineering has completed its review of the submitted plan set and cross-referenced it against the associated development package. However, as you acknowledged, Site Engineering is unable to grant final approval for Commercial Permit: TC-COM-1026-01706 until the associated revision to Development Package TD-DEV-1026-00268 has received full approval and has been issued. Please resubmit for final approval once the development package has been approved and issued by all applicable reviewers. For final approval - Ensure that all building plans match in regard to footprint, proposed height and square footage, as well as show that the downspout and structure drainage systems match with what is shown in the development package plan set.
10/21/2026 PDSD Application Completeness Express REVIEW COMPLETED