Permit Number: TC-COM-1026-01705
Parcel: 12710178F

Review Status: In Review

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1026-01705
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2026 Site Zoning APPROVED
10/21/2026 Site Engineering NOT REQUIRED
N/A Commercial Building PENDING ASSIGNMENT
N/A Commercial Mechanical PENDING ASSIGNMENT
N/A Commercial Plumbing PENDING ASSIGNMENT
N/A Commercial Post Review Express PENDING ASSIGNMENT
N/A Fire New Construction PENDING ASSIGNMENT
N/A Water - PDSD PENDING ASSIGNMENT
10/28/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1026-01705 (801 N WILMOT RD Unit:BLDG F TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide GFCI protection for all receptacles, and the clothes dryer outlet, within the laundry area, room 105. NEC 210.8(B)(14) & 210.8(D)(11).
2. Update and correct General Notes 'B', on sheet E1.0. The note states that there are 'NO' patient care areas, and then also lists 4 rooms that ARE patient care areas.
3. Outdoor Lighting Review:
Show new outdoor lighting fixture C3, with a Maximum color temperature, 3500K, OLC 402.1. Reference sheet E2.0.
4. Provide an Abbreviation list and key. Reference Sheet E3.0, panel schedule 'B', circuit designation ES-N, ESP-N, etc.
10/21/2026 PDSD Application Completeness Express REVIEW COMPLETED